ATM/Ex – Analog Pressure Transmitter

Features
• Pressure measuring range: 100 mbar … 1000 bar
• Accuracy: ≤ ± 0.50 / 0.25 / 0.10 % FS
• Operating temperature: -25 … 85°C
• Process temperature: -40 … 150°C
• Output signal: 4 … 20 mA
• Materials: Stainless steel, Titanium

Customer benefits
• Certificate: ATEX & EAC
• Fast customization thanks to configurable product design
• Demountable electrical connector option allow adjustment of zero and span setting in the field
• Compact design requires minimal space
• Short response times suitable for dynamic pressure measurements

Pressure Measuring Range (Bar)
0.1 … 0.5, (1) > 0.5 … 2 > 2 … 25 > 25 … 600, (2), (3), (4) > 600 … 1000, (2), (8)
Overpressure 3 bar 3 x FS (≥ 3 bar) 3 x FS 3 x FS (≤ 850 / ≤ 1500 bar) 1500 bar
Burst pressure, (5) > 200 bar > 200 bar > 200 bar > 850 / ≤ 1500 bar > 1500 bar
Accuracy, (6) (± % FS) ≤ 0.5 / ≤ 0.25 ≤ 0.5 / ≤ 0.25 / ≤ 0.1 ≤ 0.5 / ≤ 0.25 / ≤ 0.1 ≤ 0.5 / ≤ 0.25 / ≤ 0.1 ≤ 1 / ≤ 0.5 / ≤ 0.25
Thermal shift, (± % FS/°C)
Zero point 0 … 70°C ≤ 0.06 ≤ 0.03 ≤ 0.015 ≤ 0.015 ≤ 0.015
Zero point -25 … 85°C ≤ 0.08 ≤ 0.04 ≤ 0.02 ≤ 0.02 ≤ 0.02
Span 0 … 70°C ≤ 0.015 ≤ 0.015 ≤ 0.015 ≤ 0.015 ≤ 0.015
Span -25 … 85°C ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02 ≤ 0.02
Response time (typ.) < 1ms/10 … 90% < 1ms / 10 … 90% FS < 1ms / 10 … 90% FS < 1ms / 10 … 90% FS < 1ms / 10 … 90% FS
Long term stability, (7) < 0.5% FS / < 4 mbar < 0.2% FS / < 4 mbar < 0.1% FS / < 0.2% FS < 0.1% FS / < 0.2% FS < 0.1% FS / < 0.2% FS

Related Products