ATM.ECO/Ex – Analog Pressure Transmitter

Features
• Pressure measuring range: 100 mbar … 1000 bar
• Accuracy: ≤ ± 0.2 % FS
• Operating temperature: -40 … 125°C
• Process temperature: -40 … 150°C
• Output signal: 4 … 20 mA
• Total Error Band: ≤ ± 0.3 %FS (0 … 70°C)
• Materials: Stainless steel

benefits
• Certificates: ATEX, IECEx, EAC, GL/DNV, ABS, Lloyds
• Any measuring ranges between 0 … 100 mbar und 0 … 1000 bar available
• Static accuracy available of 0.2 % FS
• Hysteresis and repeatability better than 0.01 % FS
• Piezoresistive technology suitable for static and dynamic pressure measurements
• Modular design ideal for customization to the application
• Barometric or negative pressure ranges available

Pressure Measuring Range (Bar)
0 … 0.1 to 0 … < 1 0 … 1 to 0 … ≤ 100 0 … > 100 to 0 … ≤ 600, (2)
Overpressure 3 bar 3 x FS 3 x FS (≤ 850 / ≤ 1500 bar)
Burst pressure > 200 bar > 200 bar > 850 / > 1500 bar
Accuracy, (3) (± % FS) ≤ 0.2 ≤ 0.2 ≤ 0.2
Total Error, (4) (± % FS ; typ. / max.)
0 … 70°C compensated ≤ 0.4 / 0.8 ≤ 0.3 / 0.6 ≤ 0.7 / 1.0
-25 … 100°C compensated ≤ 0.6 / 1.0 ≤ 0.4 / 0.8 ≤ 1.0 / 1.2
-40 … 125°C compensated ≤ 0.8 / 1.4 ≤ 0.6 / 1.2 ≤ 1.0 / 1.5
Response time, (typ.) < 1ms / 10 … 90 % FS < 1ms / 10 … 90 % FS < 1ms / 10 … 90 % FS
Long term stability
(typ./max. per year)
< 1 mbar / < 2 mbar < 0.1% FS / < 0.2% FS < 0.1% FS / < 0.2% FS
0 … > 600 to 0 … 1000 0.8 … 1.2, (1) -0.05…0.05 to -0.1…0.1
Overpressure ≤ 850 / ≤ 1500 bar 3 x FS 3 bar
Burst pressure > 850 / > 1500 bar > 200 bar > 200 bar
Accuracy, (3) (± % FS) ≤ 0.2 ≤ 0.2 ≤ 0.2
Total Error, (4) (± % FS ; typ. / max.)
0 … 70°C compensated ≤ 0.7 / 1.0 ≤ 0.4 / 0.8 ≤ 0.4 / 0.8
-25 … 100°C compensated ≤ 1.0 / 1.2 ≤ 0.6 / 1.0 ≤ 0.6 / 1.0
-40 … 125°C compensated ≤ 1.0 / 1.5 ≤ 0.8 / 1.4 ≤ 0.8 / 1.4
Response time, (typ.) < 1ms / 10 … 90 % FS < 1ms / 10 … 90 % FS < 1ms / 10 … 90 % FS
Long term stability
(typ./max. per year)
< 0.1% FS / < 0.2% FS < 1 mbar / < 2 mbar < 1 mbar / < 2 mbar

Related Products

L Series With Rs232

Galltec L Series with RS232 / RS485

Economical transmitters of the L Series are primarily optimized for ambient room conditions and are very well suited to help control energy costs in HVAC and building automation applications.

4 20 Ma Pressure

4-20 mA Pressure Transmitter ATM.1ST

The ATM.1ST is an electronically compensated pressure transmitter providing a 2-wire, 4-20mA analog output. The transmitter offers accuracies of ≤ 0.05%FS or ≤ 0.1%FS including linearity, hysteresis, repeatability, zero and span setting errors.

Contact Us
By submitting this form with you information, you are indecating of our informal acceptance of our Privacy Policy