FLUXUS F532 Thermal Energy
Non-Invasive Heat and Cold Metering

NivuFlow Energy Saver
High Accurate Flow Meter + Energy Saving Capabilities for Pump Stations
FLUXUS F532 Thermal Energy
Non-Invasive Heat and Cold Metering
The FLUXUS F532 Thermal Energy is specially designed for heating and cooling measurements in industry and building applications. The new 532 platform allows for best FLEXIM performance, measurement accuracy and modern interfaces.
FLUXUS F532 TE is a compact thermal energy meter with integrated heat flow calculation for water and all water-glycol mixtures.
Based on the established transit time difference method, the volume flow is measured non-invasively with ultrasound, and the supply and return temperatures are registered via 2 temperature inputs.
The heat flow calculated in this way is determined highly dynamically and with a fast response time. Of course, totalizers for total thermal energy are also included.
FLUXUS F532 TE has USB and LAN interfaces and serves the common communication interfaces Modbus TCP, Modbus RTU, BACnet MS/TP, BACnet IP and M-Bus
100% FLEXIM performance of course also means availability of important features:
This makes the FLUXUS F532 TE not only usable as a thermal energy meter, but also for monitoring processes and plants.
As a non-invasive measuring system, it not only brings the advantage of uninterrupted installation with little effort – above all, it significantly reduces the total cost of operation. Maintenance-free, wear-free and at any time without disturbing the process.
Advantages

| Technical Facts | Measurement uncertainty of the measuring system (volumetric flow rate) | +-0,3% v.MW. +-0,005 m/s |
| Measurement uncertainty at the measuring point (volumetric flow rate) | +-1% v.MW. +-0,005 m/s | |
| Repeatability | 0,15% v.MW. +-0,005 m/s | |
| Flow velocity range | 0,01…25 m/s | |
| Pipe diameter range | 10…2400 mm (extended) | |
| Temperature Range (pipe wall) | -40°C…+130 °C | |
| Medium | water, water-glycol (0-100%) | |
| Flow channels | 1 | |
| Inputs | 2x Pt100 / Pt1000 | |
| Outputs | 1x 4-20 mA active/passive 2x Digital (pulse, binary or frequency) |
|
| Digital communication | Modbus TCP, Modbus RTU BACnet IP, BACnet MS/TP M-Bus (cannot be combined with analogue/digital outputs) |
|
| Power supply | 11…32 VDC or 110…250 VAC | |
| Advanced Meter Verification (AMV) | available | |
| Disturbance Correction | available |

High Accurate Flow Meter + Energy Saving Capabilities for Pump Stations

The ModMAG M2000 Electromagnetic flow meter has a wide selection of liner and electrode materials to help ensure maximum compatibility and minimum maintenance over a long operating period.

For portable ultrasonic flow measurements from slight to heavily polluted media using the Doppler principle in part filled and full pipes and channels.

PIOX S721 measures liquid density and concentration in real time using non-intrusive ultrasonic technology via sound velocity.