Designs available: Duct version, Wall mounting, Rod-shaped, Room version
• IP 65 with PTFE sintered filter ZE05
• Sensor tube Ø 12 mm
• Output signals available:
• RS232 or RS485 MODBUS RTU
• Operating voltage: 6…30 V DC
Special version: sealing against vibrations or condensation
Accuracy:
Humidity: ± 3% rh 30…80 % rh at 10…40 °C
Temperature ± 0,8 K 10…40 °C
Economical transmitters of the L Series are primarily optimized for ambient room conditions and are very well suited to help control energy costs in HVAC and building automation applications. Thanks to their high-quality manufacturing, these transmitters can also be used in industrial settings under moderate conditions.
| Measuring medium |
air, pressureless, non-aggressive, non-condensing |
| Min. air speed |
0.5 m/s |
| Operating temperature |
-40…+80°C |
| Storage temperature |
-40…+85°C |
| Degree of protection of measuring head |
| with protective basket ZE07 |
IP00 |
| with membrane filter ZE08 |
IP30 |
| with PTFE sintered filter ZE05 |
IP65 |
| Degree of protection housing |
IP65 |
| Material of housing |
PC (light grey / white) |
| Humidity |
| sensing element |
calibrated sensor chip calHT |
| output range |
0…100 %rh |
| accuracy |
30…80 %rh at 10…40°C ±3 %rh
< 30 %rh or > 80 %rh at 10…40°C ±5 %rh |
| Influence of temperature < 10°C or > 40°C typ. ±0.06 %rh/K |
| Temperature |
| sensing element |
calibrated sensor chip calHT |
| output ranges |
-40…+85°C |
| Accuracy |
| at 10…40°C |
±0.8 K |
| <10°C and >40°C |
see diagramm |
| Electrical data |
| Power supply, external |
6…30 VDC |
| Max. transfer distance RS232/RS485 |
15m/1000 m |
| Consumption of electronics |
< 1,0 mA |
| Directive about electromagnetic compatibility 2014/30/EU |
| DIN EN 61326-1 |
issue 07/13 |
| DIN EN 61326-1-2-3 |
issue 07/13 |