ATM/F/Ex-Hygienic Pressure Transmitter
Pressure measuring range: 100 mbar … 25 bar, Accuracy: ≤ ± 0.50 / 0.25 / 0.10 % FS, Operating temperature: -25 … 85°C, Process temperature: -25 … 100°C
The ATM.ST/N/T series is part of a comprehensive range of transmitters specifically designed for the long term monitoring of ground water, wastewater and tank level measurement. It provides a dual 4-20mA, 3 or 4 wire configuration for both level and temperature. Features such as Kevlar strengthened cable, titanium, ballast weights, dataloggers, etc. broaden the installation opportunities.
Examples of applications include:
• Deep wells, lakes, dams and reservoirs
• Bore holes
• Surface water, irrigation canals and rivers
• Wastewater and sewage treatment plants
• Tank level measurement
Features
• Fully submersible, 1″ diameter
• Titanium or 316L SS construction
• Accuracy: ≤ ± 0.1% FS or ≤ ± 0.25% FS
Includes linearity, hysteresis, repeatability AND zero and span settings
• Ranges 20″ WC to 360 psi
• Temperature Accuracy: ± 0.5°F typical
• Temperature Range 25 to 175°F
• Dual 4-20mA, 3 or 4 wire configurationlants
| Pressure Measurement | |
| Pressure ranges | Any range from 20“WC to 360 psi FS available, in any engineering units such as psi, Pa, inches H20, bar Absolute or gauge types available |
| Proof pressure | FS up to 15 psi: 45 psi FS > 15 psi up to 360 psi: 3 x FS (max. 360 psi) Consult factory for higher proof pressure |
| Operating temperature range | 25 to 175°F (process media) |
| Compensated temperature range | 25 to 175°F |
| Accuracy for pressure | ≤ ±0.1% FS ≤ ±0.25% FS Combined linearity, hysteresis, repeatability, zero and span set |
| Total Error Band (TEB) | typ. ±0.8% total for 25 to 125°F, ≤ 7.25 psi typ. ±1.3% total for 25 to 175°F, ≤ 7.25 psi typ. ±0.3% total for 25 to 125°F, > 7.25 psi typ. ±0.75% total for 25 to 175°F, > 7.25 psi |
| TEB includes linearity, hysteresis, repeatability, zero and span settings and temperature effects at max. signal span (16mA) | |
| Response time | <1ms (10 to 90%FS) |
| Long term stability | 0.1% FS/yr for pressure ranges > 30 psi Prorated for ranges below 30 psi Under standard conditions |

Pressure measuring range: 100 mbar … 25 bar, Accuracy: ≤ ± 0.50 / 0.25 / 0.10 % FS, Operating temperature: -25 … 85°C, Process temperature: -25 … 100°C

Pressure measuring range: 100 mbar … 1000 bar, Static accuracy available of 0.2 % FS, Hysteresis and repeatability better than 0.01 % FS

Pressure measuring range: 50 mbar … 1000 bar, Accuracy: ≤ ± 0.10 / 0.05 % FS, Operating temperature: -40 … 125°C, rocess temperature: -40 … 150°C

The ATM.1ST is an electronically compensated pressure transmitter providing a 2-wire, 4-20mA analog output. The transmitter offers accuracies of ≤ 0.05%FS or ≤ 0.1%FS including linearity, hysteresis, repeatability, zero and span setting errors.