Economical transmitters of the L Series are primarily optimized for ambient room conditions and are very well suited to help control energy costs in HVAC and building automation applications. Thanks to their high-quality manufacturing, these transmitters can also be used in industrial settings under moderate conditions.
• Designs available: Duct version, Wall mounting, Rod-shaped, Room version
• IP 65 with PTFE sintered filter ZE05
• Sensor tube Ø 12 mm
• Output signals available:
• 0…1 V / 0…5V / 0…10 V / 4…20 mA / passive
• Operating voltage: 12…30 V DC
• Special version: sealing against vibrations or condensation
| Four designs |
duct version (LK)
wall mounting (LW)
rod-shaped Ø 12mm (LP)
room version (LI) |
| Different physical outputs |
humidity and temp., 2 x active
humidity active / temp. passive
humidity only, active
temperature only, active or passive |
| Output signals |
0…1 V
0…5 V
0…10 V
4…20 mA (only LK and LW)
passive (temperature) |
| Special versions |
sealing for increased requirements, e.g. condensation sealing against vibrations |
| Filter |
protective basket ZE07 (IP 20)
filter with membrane ZE08 (IP30)
PTFE sintered filter ZE05 (IP65) |
| Rod-shaped sensor with 2 types of connection |
6-pin plug-in connection and assembled cable permanently attached cable |
| measuring medium |
air, pressureless, non-aggressive, non-condensing |
|
| min. air speed |
0.5 m/s |
|
| operating temperature |
|
| type LK, LW |
-40…+80°C |
|
| type LP |
-30…+80°C |
|
| type LI |
-20…+60°C |
|
| storage temperature |
-40…+85°C |
|
| degree of protection of measuring head (series LK, LW, LP) |
|
| with protective basket ZE07 |
IP20 |
|
| with membrane filter ZE08 |
IP30 |
|
| with PTFE sintered filter ZE05 |
IP65 |
|
| degree of protection of housing |
|
| type LP, LK, LW |
IP65 |
|
| type LI |
IP30 |
|
| material of housing |
|
| type LP, LK, LW |
PC (light grey / white) |
|
| type LI |
ABS (white) |
|
| electromagnetic compatibility |
ref. EN 61326 |
|
| Humidity |
| sensing element |
calibrated sensor chip calHT |
| output range |
0…100 %rh |
| accuracy |
30…80 %rh at 10…40°C ±3 %rh
< 30 %rh or > 80 %rh at 10…40°C ±5 %rh |
| influence of temperature < 10°C or > 40°C typ. ±0.06 %rh/K |
| Temperature with active output |
| sensing element |
calibrated sensor chip calHT |
| output ranges |
0…+50°C
-20…+80°C
-30…+70°C
0…+100°C |
| Accuracy |
| at 10…40°C |
±0.8 K |
| <10°C and >40°C |
s. diagramm |
| Temperature / passive output |
| sensing elements |
Pt100
Pt1000 |
| other sensing elements on demand |